low pressure water mist nozzle

Model OH-AC100

FIREKILL™ OH-AC100 Automatic pendent nozzle for OH1 up to 4,00 meter ceiling height

Min. water pressure

8 bar

Max. working pressure

16 bar

Drop size

DV90 < 300 μm

Water capacity design

72 m2 / minimum 6 nozzles

Kv metric

10.0

Flow rate at min pressure

28.3 l/min

Nominal density

2.30 mm/m2

Coverage

3.50 m x 3.50 m

Aesthetic

Aesthetic fire protection

The FIREKILL™ OH nozzles are installed recessed into the ceiling with the nozzle rosette flush with the surface and the nozzle Cover Plate protruding 10-15 mm from the surface, being the only visible parts of the nozzle in its daily use or directly into a visible pipe system in retrofit cases. The FIREKILL™ OH nozzles can be delivered in different paint and finishes making the system blend in with almost any type of surface, securing the aesthetics of the surroundings. The nozzles can also be delivered with logo print.

Description

Application

The FIREKILL™ system for protection of accommodation areas is unique as it requires very low water pressures and water flow rates. The system utilizes the automatic low-pressure water mist nozzles Model OH-AC100 which are patented pendent automatic, fine water spray nozzles. The OH-AC100 nozzle creates a homogenous fine water mist, which absorbs heat, reduces radiant heat and causes oxygen depletion near the fire, which in turn controls and suppresses the fire. This homogenous mist consists of a high concentration of very small droplets. Because of the small mass of the droplets, the nozzle creates a large coverage, further minimizing the water expenditures and hydrating nearby combustibles.

Test and Approvals

IBS Approval

The FIREKILL™ OH-AC100 has been tested in accordance VdS Fire test protocol for water mist system, protection of Office Spaces and Accommodation Areas in a ISO 17025 accredited fire test laboratory meeting the requirements in CEN EN 14972:2020.