low pressure water mist nozzle

Model OH-DC2

The FIREKILL™ Model OH-DC2, FM approved for protection of Data Processing Equipment Rooms/Halls below Raised Floors.

Min. water pressure

8 bar ≈116 psi

Max. working pressure

16 bar ≈232 psi

Drop size

DV90 < 300 μm

Water capacity design

6 nozzles

kv metric

13.85

flow rate at min pressure

39.20 l/min

Nominal density

3.00 mm/m2

Coverage

3.60 m x 3.60 m

Aesthetic

Aesthetic fire protection

The FIREKILL™ OH nozzles are installed directly into a visible pipe system. The FIREKILL™ OH nozzles can be delivered in different paint and finishes making the system blend in with almost any type of surface, securing the aesthetics of the surroundings.

Description

Application

The FIREKILL™ Model OH-DC2, FM approved for protection of Data Processing Equipment Rooms/Halls below Raised Floors is unique as it requires very low water pressures and water flow rates. The automatic low-pressure water mist nozzles Model OH-DC2 are patented automatic, fine water spray nozzles. The OH-DC2 nozzle creates a homogenous fine water mist, which absorbs heat, reduces radiant heat and causes oxygen depletion near the fire, which in turn controls and suppresses the fire. This homogenous mist consists of a high concentration of very small droplets. Because of the small mass of the droplets, the nozzle creates a large coverage, further minimizing the water expenditures and hydrating nearby combustibles.

Test and Approvals

Test and Approvals

The FIREKILL™ OH-DC2 nozzle has been successfully tested to the FM5560 Appendix N, standard for FM Data Processing Equipment Rooms/Halls Below Raised Floors Area and Local Protection.