low pressure water mist nozzle

Model NEPTUN OH-CA2

The FIREKILL™ NEPTUN OH-CA2 Low pressure water mist nozzle tested and approved to Resolution MSC.265(84) for cabin

Min. water pressure

6 bar ≈87 psi

Max. working pressure

16 bar ≈232 psi

Drop size

DV90 < 300 μm

Water capacity design

According to IMO MSC. 265(84)

kv metric

18.0

flow rate at min pressure

44.00 l/min

Nominal density

2.00 mm/m2

Coverage

5.50 m x 4.00 m

Aesthetic

Aesthetic fire protection

The FIREKILL™ NEPTUN OH nozzles are installed recessed into the ceiling with the nozzle rosette flush with the surface and the nozzle Cover Plate protruding 10-15 mm from the surface, being the only visible parts of the nozzle in its daily use or directly into a visible pipe system in retrofit cases. The FIREKILL™ NEPTUN OH nozzles can be delivered in different paint and finishes making the system blend in with almost any type of surface, securing the aesthetics of the surroundings.

Design

Application

The FIREKILL™ NEPTUN OH system for protection of cabins are unique as it requires very low water pressures and water flow rates. The system utilizes the automatic low-pressure water mist nozzles Model OH-CA2 which are patented automatic, fine water spray nozzles. The OH-CA2 nozzle create a homogenous fine water mist, which absorbs heat, reduces radiant heat and causes oxygen depletion near the fire, which in turn controls and suppresses the fire. This homogenous mist consists of a high concentration of very small droplets. Because of the small mass of the droplets, the nozzle creates a large coverage, further minimizing the water expenditures and hydrating nearby combustibles.

Test and Approvals

DnV MED-B and UK MER-B Approval

The FIREKILL™ NEPTUN OH-CA2 has been tested in accordance with IMO Resolution MSC.265(84) for cabins. The FIREKILL™ NEPTUN OH-CA2 can therefore be used for IMO Occupancy classification (6) Accommodation space minor fire risk, (7) Accommodation spaces of moderate fire risk, (9) Sanitary & similar spaces