Defined application
ACCU Charging station
Min working pressure
2 Bar
Max working pressure
10 Bar
Drop size
DV90 = 300 um
Coverage
Depending on size
SUFA Valve Kv metric
97
SUFA Valve connection
3/4" BSP
Nozzle Kv Metric
1.1
Design run time
10 minutes
Defined application
Application
The VID FIREKILL lModel ACCU Tool Cabinet protection has been designed and tested to protect charging stations for ACCU tools stored in a cabinet. It consist of a SUFA Control Valves which has been designed to provide fire protection of localized areas. The SUFA valves enables system designers and installers to tailor sprinkler systems or low-pressure water mist systems to specific locations and applications. In addition to the SUFA Control valve a 22 mm N-Pipe with predrilled M10 holes for the low pressure water mist nozzle Model F1 and a pressure switch with set point 2 bar increasing pressure.
Defined application
Test
The FIREKILL low pressure water mist system for ACCU Charging stations has been tested in a steel cabinet H-1800 mm x D - 360 mm x W - 950 mm with 5 shelfs and 10 nozzles.