Defined application

ACCU Charging station

The FIREKILL™ Model ACCU Tool Cabinet protection has been designed and tested to protect charging stations for ACCU tools stored in a cabinet.

Min working pressure

2 Bar

Max working pressure

10 Bar

Drop size

DV90 = 300 um

Coverage

Depending on size

SUFA Valve Kv metric

97

SUFA Valve connection

3/4" BSP

Nozzle Kv Metric

1.1

Design run time

10 minutes

Defined application

Application

The VID FIREKILL lModel ACCU Tool Cabinet protection has been designed and tested to protect charging stations for ACCU tools stored in a cabinet. It consist of a SUFA Control Valves which has been designed to provide fire protection of localized areas. The SUFA valves enables system designers and installers to tailor sprinkler systems or low-pressure water mist systems to specific locations and applications. In addition to the SUFA Control valve a 22 mm N-Pipe with predrilled M10 holes for the low pressure water mist nozzle Model F1 and a pressure switch with set point 2 bar increasing pressure.

Defined application

Test

The FIREKILL low pressure water mist system for ACCU Charging stations has been tested in a steel cabinet H-1800 mm x D - 360 mm x W - 950 mm with 5 shelfs and 10 nozzles.

element_right