low pressure water mist nozzle
ETNA Galley exhaust duct
Min. water pressure
6.0 Bar
Max. working pressure
16.0 bar ≈132 psi
Duct dimension
0.6 m x 0.3 m / ø 0.57 m
Drop size
DV90 < 300 μm
Water capacity design
Acc. to regulations
KV METRIC
0.90
FLOW RATE AT MIN PRESSURE
2.20 l/min at 6 bar
NOMINAL DENSITY
7.38 mm/m2
Aesthetic
Aesthetic fire protection
The FIREKILL™ ETNA N-Pipe is a small size system for protecting Galley exhaust duct. It can be installed inside the duct hiding from the surroundings.
Design
Application
The FIREKILL™ ETNA N-Pipe is designed for protection of Galley exhaust duct. It can be supplied in different variants depending on the design of the system. The system is supplied in stainless steel as a purely piped system or with flexible hoses for easy installation.
Test and approvals
DnV MED-B and UK MER-B approval
The FIREKILL™ ETNA N-Pipe is approved by DnV as it has been successfully tested to ISO 15371 Ships and marine technology – Fire-extinguishing systems for protection of galley cooking equipment.