Stand alone
SASWP
Water cylinder capacity
120 l
Water cylinder material
AISI 306
Water cylinder pressure class
PN 16
Water cylinder standard
PED EN 13445
N2 Cylinder capacity
33 l and 67,5 l
N2 Cylinder pressure class
200 Bar
N2 cylinder standard
TPED 2010/35/EU
Hoses and fittings
AISI 316
Stand alone system
Application
The FIREKILL Low Pressure Water Mist Stand Alone Systems Model SAS-WP is a modular stand-alone low pressure watermist system for protection of ordinary hazard using automatic nozzles. The low pressure water mist effect is achieved by using compressed gas to pressurise a water cylinder which in turn forces the water through the system and the nozzles. The SAS-WP activates based on pressure drop in a sensor line connected to the first water cylinder. The pressure drop is caused by an activated nozzle within the protected space.
Stand alone system
Description
The FIREKILL Low Pressure Water Mist Stand Alone Systems consist of stainless steel water cylinders and standard high pressure nitrogen cylinder. The water cylinders does not need to be removed for neither refilling through the top connection or emptied through the bottom drain connection. The water cylinders can also be supplied with a level indicator using a float with 3 alarm settings, 10%, 50% and 90% filling. The system supply includes stainless steel hoses and fittings for connection between the N2 pressure regulator and also the connection between the cylinders.