Stand alone

SASWP

The FIREKILL™ Model SASWP is a modular stand-alone low pressure watermist system using automatic nozzles

Water cylinder capacity

120 l

Water cylinder material

AISI 306

Water cylinder pressure class

PN 16

Water cylinder standard

PED EN 13445

N2 Cylinder capacity

33 l and 67,5 l

N2 Cylinder pressure class

200 Bar

N2 cylinder standard

TPED 2010/35/EU

Hoses and fittings

AISI 316

Stand alone system

Application

The FIREKILL Low Pressure Water Mist Stand Alone Systems Model SAS-WP is a modular stand-alone low pressure watermist system for protection of ordinary hazard using automatic nozzles. The low pressure water mist effect is achieved by using compressed gas to pressurise a water cylinder which in turn forces the water through the system and the nozzles. The SAS-WP activates based on pressure drop in a sensor line connected to the first water cylinder. The pressure drop is caused by an activated nozzle within the protected space.

Stand alone system

Description

The FIREKILL Low Pressure Water Mist Stand Alone Systems consist of stainless steel water cylinders and standard high pressure nitrogen cylinder. The water cylinders does not need to be removed for neither refilling through the top connection or emptied through the bottom drain connection. The water cylinders can also be supplied with a level indicator using a float with 3 alarm settings, 10%, 50% and 90% filling. The system supply includes stainless steel hoses and fittings for connection between the N2 pressure regulator and also the connection between the cylinders.